Datacenters :: Chicago, IL

General Information




Facility Provider DuPont Fabros Technology, Inc
Commissioned 2008
Building Area 485,000(sq ft) gross - 221,000(sq ft) raised floor
Parking 518 spots onsite

Computer Room Specifications (Per Room)




Raised Floor Space 10,000 square feet (approx.)
Colocation Space 6,200 square feet
Electrical Capacity 1,300kW of critical load
Power Density 210 watts/sqft, up to 12kW/cabinet supported
Floor Load Capacity 450psf
Building Type Single story, raised floor
Raised Floor Height 42"
Fire Suppression Laser-based Very Early Smoke Detection
Pre-action zoned dry-pipe system
Redundancy Minimum N+1 on all systems

Facility Information




Primary Voltage 34.5kV
# of Utility Feeders 2
# of Power Transformers 8
UPS 16 - 1,300kW rotary powered systems
Standby Power 16 - 2,250kW diesel generator systems
Fuel Capacity 100,000 gallons of diesel
Cooling System 8 - 1,150 ton centrifugal chillers
Thermal Energy Storage 500,000 gallons of chilled water
Data Pathways 2 diverse fiber vaults for redundant entry
Roof Access Available
Loading Dock 4 enclosed and heated bays, hydraulic levelers
Office Space Up to 40,000 square feet of contiguous space available in attached building

Security




Building and Perimeter Bullet-resistant protection at security check-in level III walls and doors
Security Staff 24/7/365 staffing with at least 2 officers
Access Control Dual-factor authentication system (keycard + biometrics)
Alarm System Yes
Closed Circuit TV Camera surveillance archived onsite and offsite