Datacenters :: Dallas, TX
General Information
Facility Provider COLO4
Commissioned Year 2000
Building Area 68,000(sq ft) raised floor datacenter space
Parking 148 spots onsite
Computer Room Specifications
Raised Floor Space 68,000 square feet (approximately)
Colocation Space 32,200 square feet
Electrical Capacity 12.5 MW utility power
Power Density 250 watts/sqft, up to 12kW/cabinet supported
Floor Load Capacity 300psf
Building Type Single story, raised floor
Raised Floor Height 30"
Fire Suppression Laser-based Very Early Smoke Detection
Pre-action zoned dry-pipe system
Redundancy Minimum N+1 on all systems
Facility Information
# of Utility Feeders 2
# of Power Transformers 4
UPS 8 - 1,300kW rotary powered systems
Standby Power 4 - 2,250kW diesel generator systems
Fuel Capacity 10,000 gallons of diesel
Cooling System Redundant HVAC with Liebert air handlers
CRAC SYSTEM Each unit supported by independent condenser
Data Pathways 2 diverse fiber vaults for redundant entry
Roof Access Available
Loading Dock 1 loading bay with hydraulic leveler
Office Space Work area and conference room available for customer use 24/7/365
Security
Building and Perimeter Bullet-resistant protection at security check-in level III walls and doors
Security Staff 24/7/365 staffing with at least 2 officers
Access Control Dual-factor authentication system (keycard + biometrics)
Alarm System Yes
Closed Circuit TV Camera surveillance archived onsite and offsite